For a modbus source to be normalized by Intelie Live, two files are needed to be configured, the sources.xml and the modbus.json. The specific setting about a modbus source can be found at the modbus protocol page. Following the example at the modbus protocol page, two <request> objects need to be mapped on the following JSON format (modbus.json).

LiveRig Collector 5.0.0 or above

{
  "version": "2.0",
  "controllers": {
    "pump-pressure-1": [
      {
        "type": "input-register",
        "start_address": 1,
        "count": 3,
        "unit": "bar",
        "alias": ["rotary_pump_pressure", "rotation_max_pressure", "hold_back_pressure"]
      },
      {
        "type": "discrete-input",
        "start_address": 5,
        "count": 2,
        "alias": ["water_pressure"]
      },
      {
        "type": "coil",
        "start_address": 10
      }
    ],
    "water-flow-1": [
      {
        "type": "holding-register",
        "start_address": 1,
        "unit": "ft3/d",
        "dataType": "uint16"
      },
      {
        "type": "coil",
        "start_address": 3
      }
    ]
  }
}

Each controller in the field controllers represents a device defined on sources.xml at <request>/<object> and it describes all memory areas that will be fetched. Each memory area has the following fields:

NameDescriptionIs required?Default value

type

The modbus register type to be fetched. This can be input-register, holding-register, discrete-input and coil

Yes

-

start_address

A number, between 1 and 65536. Represents the starting address of the memory area. OBS: the end device could have address mapping differences. For example: returning the value for address 99 when we declared address 100. Please check if it is the case and adjust accordingly.

Yes

-

count

Represents the number of registers or coils that will be read sequentially from the start_address.

No

1

unit

The unit of measurement to be used by Intelie Live

No

-

alias

A rename for the channel when sent to Intelie Live. See more info below

No

The default channel name uses the format {type}_{address}

dataType

The data type to parse the values returned by the Modbus source. See more info below

No

If the register type is coil or discrete-input, the default dataType will be boolean. Otherwise the default dataType is int16

Data Types

The dataType field from the modbus.json file can have the following options on the modbus.json file:

  • Single Register:

    • boolean (1 bit)

    • int8 (8 bits)

    • uint8 (8 bits)

    • byte (8 bits)

    • int16 (16 bits)

    • uint16 (16 bits)

    • word (16 bits)

    • char (8 bits)

    • wchar (16 bits)

  • Double Register (32 bits):

    • int32

    • uint32

    • float

    • word32

  • Quadruple Register (64 bits):

    • int64

    • uint64

    • double

    • word64

Using a data type that requires more than 1 register will disable the count feature declared at the modbus.json file.

You don't need to declare a count if using Multi-register data types, we will assume it is always the next address. Example: If the dataType is int32 and the start_address is 123, the LiveRig Collector will fetch the values from addresses 123 and 124 to form the int32 (long) value.

Aliases

The alias field from the modbus.json file is an array of strings. That means that you can allocate more than 1 alias to a memory area. If that is the case the alias will be applied by the following rule: For each address fetched by the memory area, we will apply the alias from the list using the order of both.

Example 1: If a memory area has a start_address set as 123 and a count set as 3, the end result will be values from addresses 123, 124 and 125. If the alias field has just the value ["exampeAlias"], then the LiveRig Collector will map exampeAlias_123 to address 123, exampeAlias_124 to address 124 and exampeAlias_125 to address 125.

Example 2: If a memory area has a start_address set as 123 and a count set as 3, the end result will be values from addresses 123, 124 and 125. If the alias field has the value ["exampleAlias1", "exampleAlias2", "exampleAlias3" ], then the LiveRig Collector will map exampleAlias1 to address 123, exampleAlias2 to address 124 and exampleAlias3 to address 125.

Example 3: If a memory area has a start_address set as 123 and a count set as 3, the end result will be values from addresses 123, 124 and 125. If the alias field has the value ["exampleAlias1", "exampleAlias2", "exampleAlias3" , "exampleAlias4"], then the LiveRig Collector will map exampeAlias_123 to address 123, exampeAlias_124 to address 124 and exampeAlias_125 to address 125. The exampleAlias4 will not be used as a channel rename.

Note: If there is fewer aliases than the address count (the alias list has a size of 2 and the count of addresses is 4), the LiveRig Collector will raise an exception, since it won't know how to map the aliases to each address.

LiveRig Collector 4.x or bellow

{
  "controllers": {
    "pump-pressure-1": {
      "input-register" : {
        "start_address": 0,
        "count": 3,
        "unit": "bar"
      },
      "discrete-input": {
        "start_address": 5,
        "count": 2,
        "unit": "psi"
      },
      "coil": {
        "start_address": 10
      }
    },
    "water-flow-1": {
      "holding-register" : {
        "start_address": 0,
        "unit": "ft3/d"
      },
      "coil": {
        "start_address": 3
      }
    }
  }
}

Each controller represents a device defined on sources.xml at <request>/<object> and describe all memory areas that will be fetched. For each memory area (such as input-register, discrete-input, coil or holding-register), the following information must be provided:

NameDescriptionIs required?Default value

start_address

A number, between 1 and 65536. Represents the starting address of the memory area

yes

count

Represents the number of registers or coils that will be read sequentially from the start_address

No

0

unit

The unit of measurement to be used in Intelie Live

No